Experimental study on applicability of compressed air foam fire water using seawater in train fire at subsea tunnel rescue station

(사)한국터널지하공간학회 / (사)한국터널지하공간학회, (P)2233-8292; (E)2287-4747
2017, v.19 no.5, pp.705-715
https://doi.org/10.9711/KTAJ.2017.19.5.705






  • Downloaded
  • Viewed

Abstract

In this study, applicability of compressed air form (CAF) fire water was verified in abid to use the undersea effluent as fire water. Foam collector was fabricated inaccordance with KS B ISO 7203-1 (Specification for low expansion foam concentratesfor top application to water-immiscible liquids) and the test was conducted using freshwater as fire water for 19 times and using seawater as fire water 15 times that totaled34 times. Foam reduction time was 237.73 seconds on average with fresh water and215.60 seconds with seawater, which proved the applicability of CAF fire water usingseawater. Besides, window breaker was fabricated to directly extinguish the fire intrain and a full-scale fire test was conducted three times. At the final 3rd test, windowglass was broken in 2 seconds to make the hole for fire extinguishing and suppressedthe fire in 3 seconds using CAF fire extinguisher.

keywords
CAF (Compressed Air Foam), Foam Fire Extinguishing System, Foam Collector, Window Breaker, Tunnel Safety Facility, 압축공기포(Compressed Air Foam), 포 소화설비, 포 수집기, 창문 파괴장치, 터널 방재 설비

Reference

1.

1. Park, B.J., Shin, H.J., Yoo, Y.H., Park, J.O. Kim, H.S. (2016), “Evaluation test of applicability of Compressed Air Foam fire extinguishing system for train fire at rescue station in Subsea tunnel”, Journal of Korean Tunnelling and Underground Space Association, Vol. 18, No. 5, pp. 413-418.

2.

2. Lee, J.W., Lim, W.S., Kim, S.S., Rie, D.H. (2012), “A study on fire extinguishing performance evaluation of compressed air foam system”, Transactions of Korean Institute of Fire Science and Engineering, Vol. 26, No. 5, pp. 73-78.

3.

3. Lee, J.W., Lim, W.S., Rie, D.H. (2013), “A Study on b class fire extinguishing performance of air ratio in the compressed air foam system”, Transactions of Korean institute of fire science and engineering, Vol. 27, No. 6, pp. 8-14.

4.

4. Kim, A.K., Crampton, G.P. (2012), “Evaluation of the fire suppression effectiveness of manually Ap, plied Cmpressed-Air-Foam (CAF) System”, Fire Technology, Vol. 48, No. 3, pp. 549-564.

5.

5. Fire Extinguishing Media (2014), Specification for low expansion foam concentrates for top application to water-immiscible liquids (ISO 7203-1), pp. 20-27.

6.

6. Fire Emergency Management (2012), Fire safety criteria of doam fire extinguishing system (NFSC 105), pp. 1-10.

7.

7. National Fire Protection Association (2005), Standard for low, medium, and high-expansion foam (NFPA 11), pp. 130-140.

(사)한국터널지하공간학회