Fire resistance assessment of precast fireproof duct slab

(사)한국터널지하공간학회 / (사)한국터널지하공간학회, (P)2233-8292; (E)2287-4747
2020, v.22 no.6, pp.669-680
https://doi.org/10.9711/KTAJ.2020.22.6.669






  • Downloaded
  • Viewed

Abstract

In Korea, fireproof performance is evaluated through a series of fire-resistance tests for important structures, and the performance standard follows the guidelines suggested by ITA. The fireproof duct slab manufactured by combining the slab and the fireproof material with a precast method is effective in that it can eliminate the construction time of the fireproof material. In this study, a series of fire resistance tests was performed on the fire test specimens under the RWS fire scenario in order to secure the fire resistance performance of the precast fireproof duct slab. As a result of the test, it was found that the fireproof performance was secured when the thickness of the fireproof material was 30 mm or more. In both fireproof materials and concrete, the rate of temperature change initially increased, then decreased, and then increased again, and the temperature at the inflection point was measured as 110°C for all fireproof materials and concrete. It is judged that this occurs when the C-S-H(CaO-SiO2-H2O) generated by the hydration reaction in both the fireproof material and concrete is dehydrated.

keywords
터널, 화재, 풍도슬래브, 내화, 온도, Tunnel, Fire, Duct slab, Fireproofing, Temperature